CLEAN ROOM CDP

Product details

GENERAL Highly efficient recessed luminaire for direct illumination. Full visual comfort is ensured with the latest optical and electrical components. 

OPTICS Highly transparent diffuser of microprismatic structure provides glare limitation and a uniform, diffused light. Opal foil provides a uniformly illuminated surface, without visible light sources. Protector of tempered glass provides a smooth surface for easy maintenance.

LIGHTING MANAGEMENT The choice of adequate control gear enables lighting management. 

HOUSING Housing is made of steel sheet 0.8mm thick. The final coating is a special antibacterial white epoxy polyester powder, resistant to aggressive cleaning agents. The luminaire is sealed, while the construction and modality of mounting provide complete sealing with the ceiling. 

APPLICATIONThe luminaire is intended for use in monolith and panel ceilings. 

EQUIPMENT Supplied with mounting kit.

ADDITIONAL This luminaire can be optionally equipped with an EM module, enabling operation in the case of a power failure, both with the proper autonomy and with the central battery system (CBS). Zinc primer housing coating for corrosion prevention or other light colour temperatures are available upon request.

Technical data

recessed ceiling
Antimicrobial RAL9003 white powder coating smooth glossy
CE marking
mounting on normally flammable surfaces
electrical safety
ingress protection
lamp type
voltage
frequency
* Please select the row to enable viewing and downloading of additional material.
Order code Description A/B/H[mm] a/b/h[mm] WEIGHT [kg] FLUX [lm]* IP UGR Total Power [W] CCT [K] CRI Led Service Life
9021119XY CLEAN ROOM CDP 600 /840 HE 595/595/105 580/580/140 8.00 3754 IP65 <19 32.0 4000 >80 60000h L90B10 /SDCM3
9021121XY CLEAN ROOM CDP 600 /840 HO 595/595/105 580/580/140 8.00 5465 IP65 <19 47.0 4000 >80 60000h L90B10 /SDCM3
9021126XY CLEAN ROOM CDP 1200 /840 HE 1195/295/105 1180/280/140 9.00 3645 IP65 <19 32.0 4000 >80 60000h L90B10 /SDCM3
9021127XY CLEAN ROOM CDP 1200 /840 HO 1195/295/105 1180/280/140 9.00 5306 IP65 <19 47.0 4000 >80 60000h L90B10 /SDCM 3
9021219XY CLEAN ROOM CDP 600 /940 HE 595/595/105 580/580/140 8.00 3729 IP65 <19 33.0 4000 >90 60000h L90B10 /SDCM3
9021221XY CLEAN ROOM CDP 600 /940 HO 595/595/105 580/580/140 8.00 5454 IP65 <19 51.0 4000 >90 60000h L90B10 /SDCM3
9021226XY CLEAN ROOM CDP 1200 /940 HE 1195/295/105 1180/280/140 9.00 3621 IP65 <19 33.0 4000 >90 60000h L90B10 /SDCM3
9021227XY CLEAN ROOM CDP 1200 /940 HO 1195/295/105 1180/280/140 9.00 5296 IP65 <19 51.0 4000 >90 60000h L90B10 /SDCM3
* Luminaire luminous flux and connected electrical load - initial tolerance of ±10 % (at ambient temperature of 25° C).

Lighting solutions you need

Cookies allow page content to be adapted according to the needs of users, thus providing improved functionality and an improved user experience. Cookies can also be used to analyze the use of websites, as well as for advertising purposes. By clicking on "I accept" you agree to the use of cookies. You can change your cookies settings at any time.